PTZ Data Surge Protector

STR201D

STR201D

1-CH RS485 Data Surge Protector
Features:
Application in the equipment over voltage &over currency protection. Special in industry controller network, RS422/485 interface signal, auto-control and instrument line, data line, telephone equipment, fax etc.  Protect them from the over-Voltage, over-Currency, electrostatic discharge etc.; The main traits as follows:Multi-level protection, width capacity, low limit-voltage, fast response time, Low insertion loss, high speed and so on
Working Principle:
Surge protector link to the be protected front-end equipment, when transmission lines were happen to the lightning and other instantaneous overvoltage shock, the impulse current through the surge protector protection branch will discharge into the earth, and the output voltage limit in the device allow voltage range. ensure the safety of operation 



Specifications:
Temperature:-40℃~70℃;
Relative humidity≤95%;
Atmospheric pressure70kPa~106 kPa.
 
model STR201D
Nominal working voltage Un(V) 12 24
Max continuous operation voltage Uc(V) 15 36
Nominal discharge current  In(8/20ms)(KA) 5 5
Max discharge current Imax(8/20ms)(KA) 10 10
Protection level Up 10/700/ms
(V)
≤30 ≤60
Insertion lossed(dB) ≤0.5 ≤0.5
Transmission rate Vs 2 M 2 M
Response time Ta ≤1ns
Protection line One pairs
Shell protection level IP20
Dimension 50*25*25mm
Shell material Aluminum
Interface type Interface 2 pin (RS422/RS485)




Installations, Use and Maintenance:   

1 Installation steps
* Protectors access system before, first check grounding resistance,
   generating should comply with the requirements specification.
* Protectors by protection equipment front-end, access to reliable
   connect.
* Using short and thick grounding lines as possible as you can to
   connect with the Earth-termination system.
2 Precautions:
* Protectors have input (IN), output (OUT) mark, output terminal
  and protected, don't connect the device to connect. Otherwise it
  will cause the protector the damage, the equipment can be protected.
* Due to plug sockets connected factors such as loss of poor should
   be caused by increased connected or replace protector.
* Users Can’t removes protector of each fasteners parts, in case cause
   damage, affect the normal work.
3 Protector examination
* With triple-use measure table "Ω x 1" measurer the input middle-line
   and output middle-line of the protector, the resistance should in
   between about 4.7 Ω; If open, do not normal, protector should be
   replaced.
* With triple-use measure table "Ω x 10K" measurers the line-line
   resistance ,the result need to be 400 Ω, line-surge earth-grounding
   resistance need be ∞, If not, the protector should be replaced.


 
Product appearance and the installation instructions:


Class Date Title Download
Datasheet 2017-06-16 STR201D