HD PVD Surge Protector

STR201PVD24-HD

STR201PVD24-HD

1-CH 24V Power & Video & Data Signal Surge Protector
Features:
●Single Channel Power +Video +Data Signal Surge Protector
●Standard:IEC61643-21:2000
●Protect AC24V power,video and data at the same time
●Multilevel protection: Overvoltage protect ,large Flow capacity 
  Low limiting voltage, faster Response,less Insertion loss
●Ground connection: directly to ground
●Nice Design, mini size,easy to installation
Working Principle:
Surge protector link with the equipment which be protected in the front of the system. When transmission lines were happen to the lightning and other instantaneous overvoltage shocked, the impulse current through the surge protector grounding cables discharging into the earth, and limit output the voltage with the device allow -voltage. Ensure the safety of the equipment.



Specifications:
Temperature:-40℃~70℃;
Relative humidity≤95%;
Atmospheric pressure70kPa~106 kPa.
Model STR201PVD24V
  Video Power Control
Nominal working voltage Un 5V 24V 5V
Max continuous working voltage Uc 6V 36V 6V
Nominal discharge current In(8/20μs) 5KA 5KA 5KA
Max discharge current Imax(8/20μs) 10KA 10KA 10KA
Protection Level Up(10/700/μs) <20V   <20V
Protection Level Up(8/20μs)   <200V  
Standard load current IL   ≤3A 2A
Leakage current IA ≤5μA  
Response time Ta ≤1ns ≤25ns 1ns
Insertion loss db ≤0.2dB   ≤0.2dB
Band width FG (0.3~10)M (0.3~2)M
Transmission rate Vs

10M

 

2M

Protection grade IP20
Dimension 98*66*29 mm
Material Aluminum
Interface(optional) BNC(K/K、K/J) Terminal 2Pin Terminal 2 pin






































Installations, Use and Maintenance:   

1 Installation steps
* Before connecting the protector to the system, Make sure check
   grounding resistance and conform to the criteria with the requirements;
Connect the protector to the front of the device firmly.
Use the short and thick grounding lines as possible as you can
   to connect with the Earth-termination system.
2 Note:
There are IN and OUT icons marked on the protector, and
  the OUT port should be connected with the protected device,
  please don’t make mistake. Or it will cause damage to the
  protector, and also the device can’t be protected as expect.
Due to sockets connected interface factors caused the loss of
  poor, should be replace the protector or maintenance.
Users Can’t removes the fasteners part of the device, in order
  to avoiding damage and affect the normal work.
3 Protector examination
Protector no needs special maintenance, in case the protector
  shocked by high voltage, the Led lights will power off, it means
  need to replace or maintain the protectors
Use the Multi-meter with "Ω × 1" range to measure the protector’s
  resistance, the value should be around 0 Ω ; If not, protector need to
  be replaced.
*Use the Multi-meter with "Ω × 10K" range to measure the middle
  line to earth-ground resistance, the value will be around 400KΩ,
  if not , need to replace the protector.
 
 
Product appearance and the installation instructions:
 
 
 
 
 
 
 
 
 
 
 
 
Class Date Title Download