Power Surge Protector

STR201P/12

STR201P/12

1-CH 12V Power Signal Surge Protector
Features
●Single Channel Power Signal Surge Protector
●Standard:IEC61643-21:2000
●Protect 12V power and video at the same time
●Multilevel protection: Overvoltage protect ,large Flow capacity 
  Low limiting voltage, faster Response,less Insertion loss
●Ground connection: directly to ground
●Nice Design, mini size,easy to installation
Working Principle:
Surge protector link with the equipment which be protected in the front of the system. When transmission lines were happen to the lightning and other instantaneous overvoltage shocked, the impulse current through the surge protector grounding cables discharging into the earth, and limit output the voltage with the device allow -voltage. Ensure the safety of the equipment.



Specifications:
Temperature:-40℃~70℃;
Relative humidity≤95%;
Atmospheric pressure70kPa~106 kPa. 
Model STR201P12V
Nominal working voltage Un(V) 12
Max continuous operation voltage Uc(V) 18
Nominal discharge current In(8/20ms)KA 5
Max discharge current Imax(8/20ms)KA 10
Protection Level Up( 10/700ms)V 24
Response time Ta 25ns
Shell protection level IP20
Dimension 65*26*26 mm
Shell material Aluminum
Interface type Terminal 2Pin




Installations, Use and Maintenance:   
1 Installation steps
* Before connecting the protector to the system, Make sure
   check grounding resistance and conform to the criteria with
   the requirements;
* Connect the protector to the front of the device firmly.
* Use the short and thick grounding lines as possible as you can
   to connect with the Earth-termination system.
2 Note:
There are IN and OUT icons marked on the protector, and
   the OUT port should be connected with the protected device,
   please don’t make mistake. Or it will cause damage to the protector,
   and also the device can’t be protected as expect.
Due to sockets connected interface factors caused the loss of poor,
  should be replace the protector or maintenance.
Users Can’t removes the fasteners part of the device, in order to
   avoiding damage and affect the normal work.
3 Protector examination
* Use the Multimeter with "Ω × 1" range to measure the protector’s
   resistance, the value should be around 0 Ω ; If not, protector need to
   be replaced.
* Use the Multimeter with "Ω × 10K" range to measure the middle
   line to earth-ground resistance, the value will be around 400KΩ, if not ,
   need to replace the protector.
 
Product appearance and the installation instructions:


Class Date Title Download
Datasheet 2017-06-16 STR201P 12